Measurement Technique / Pressure Measurement / Pressure Transmitter

Model IXLDP

differential pressure transducer

Attributes:
- NEMA 4X metal construction
- High overpressure limits
- Six types of output signals available
- 5:1 turndown option
- Variable dampening option
- On-board voltage regulation allows use of lower cost, non-precise, unregulated power supply
- Accuracy: 0.5 %, 0.25 %
- Metric Range Min: 0 ... 0,25 mbar
- Metric Range Max: 0 ... 500 mbar
- Imperial Range Min: 0 ... 0.1 in. H2O
- Imperial Range Max: 0 ... 200 in. H2O
- Lab/Clean room monitoring, Leak detection, Laminar flow, Furnace draft measurement, Medical diagnostic equipment, Over air flow control

technical data

Model DXLDP

differential transducer

Attributes: 
- The exclusive patented Ashcroft® SpoolCal™ actuator provides in-place system calibration without disturbing process tubes
- Front access test jacks provide on-line signal reference without removing wiring 
- LED range status indicators for instant troubleshooting information
- DIN Rail Mount – dramatically reduces installation and calibration costs
- 2:1 range turndown options
- On-board voltage regulation allows use of lower cost, unregulated power supply
- Metric Range Min: 0 ... 0.25 mbar
- Metric Range Max: 0 ... 125 mbar
- Imperial Range Min: 0 ... 0.1 in. H2O
- Imperial Range Max: 0 ... 50 in. H2O
- High reliability HVAC, bio-pharm, bio-tech, room pressurization and control, velocity pressure

technical data

Model CXLDP

differential transducer 

Attributes:
- Rugged ABS package capable of DIN rail or standard panel mounting
- LED power status indicator to assist in trouble shooting or quickly locating the instrument in a duct
- Detachable DIN style terminal block reduces wiring errors and field wiring time
- 25 standard pressure ranges all capable of withstanding 1 bar without damage or calibration change
- Digitally compensated, 0.4 % F.S. and 0.8 % F.S. accuracy models
- NIST traceable
- Metric Range Min: 0 ... 25 Pa
- Metric Range Max: 0 ... 6 kPa
- Imperial Range Min: 0 ... 0.1 in. H2O
- Imperial Range Max: 0 ... 25 in. H2O
- Static or velocity pressure measurement for four stations, ducts, building pressure, filter efficiency, VAV boxes or room pressurization.

technical data

Model DXD

differential pressure transducer

Attributes:
- Stainless Steel & Lexan NEMA 1 construction
- High overpressure protection
- Five types of output signals available
- Mounts inside standard 3-1/2 electrical box
- Board level OEM versions available
- On-board voltage regulation allows use of lower cost unregulated power supply
- Accuracy: 1 %
- Metric Range Min: 0 ... 0,25 mbar
- Metric Range Max: 0 ... 500 mbar
- Imperial Range Min: 0 ... 0.1 in. H2O
- Imperial Range Max: 0 ... 50 in. H2O
- HVAC, fume hood control, lab/clean room pressurization, laminar flow, leak detection, medical, fan tracking, glovebox and velocity measurements.

technical data